ANALYSIS OF SUITABLE METHODOLOGIES FOR COMPRESSOR MASS FLOW RATE CORRECTION TO OTHER SUPERHEAT LEVELS AND REFRIGERANTS

Autores/as

DOI:

https://doi.org/10.21134/a92j4393

Palabras clave:

Compressor Performance, Mass flow rate, Superheat, Suction Temperature, Extrapolation capability

Resumen

This paper investigates the impact of suction conditions and refrigerant on scroll compressor mass flow rate by using calorimeter tests from AHRI-11 and AHRI-21 reports, published by AHRI's Low-GWP Alternative Refrigerants Evaluation program.

Two Copeland scroll compressors (20 and 51 cm3) have been analyzed including different suction conditions (SH = 11K, SH = 22K, Ti = 18ºC) and several refrigerants (R134a, R32, R410A, R404A, etc.). Previous studies have explored response surfaces for energy consumption and mass flow rate variables.

This study aims to expand the analysis by identifying the optimal approach to extrapolate mass flow rate from specific suction conditions to others SH or suction temperature levels and refrigerants. The current compressor characterization standard relies on the 1981 Dabiri correlation to correct compressor mass flow rate with suction conditions. Thus, this study aims to assess the adequacy of this correction and explore alternative correction methods for improved results.

Referencias

ERENCES

Thermal Area IUIIE, IMST-ART: A simulation tool to assist the selection, design and optimization of refrigeration equipments and components, IMST-GROUP, Instituto de Ingeniería Energética, UPV.

J. Brown, R. Brignoli, P. Domanski, Y. Yoon, CYCLE_D-HX: NIST vapor compression cycle model accounting for refrigerant thermodynamic and transport properties; version 2, user’s guide, (2021).

H. Cheung, S. Wang, A comparison of the effect of empirical and physical modeling approaches to extrapolation capability of compressor models by uncertainty analysis: A case study with common semi-empirical compressor mass flow rate models, International Journal of Refrigeration 86 (2018) 331–343.

AHRI, AHRI-540. Performance Rating of Positive Displacement Refrigerant Compressors, (2020).

A.E. Dabiri, C.K. Rice, Compressor-simulation model with corrections for the level of suction gas superheat, Oak Ridge National Lab., TN (USA); Science Applications, Inc., La Jolla, CA (USA), 1981.

J. Jacobs, Analytic and Experimental Techniques for Evaluating Compressor Performance Losses, International Compressor Engineering Conference (1976).

S. Shrestha, I. Mahderekal, V. Sharma, O. Abdelaziz, TEST REPORT #11. Compressor calorimeter test of R-410A alternatives R-32, DR-5, and L-41a, Oak Ridge National Laboratory, 2013.

S. Shrestha, V. Sharma, O. Abdelaziz, TEST REPORT #21. Compressor calorimeter test of R-404A alternatives ARM-31a, D2Y-65, L-40, and R-32/R-134a (50/50), Oak Ridge National Laboratory, 2013.

E. Winandy, C.S. O, J. Lebrun, Experimental analysis and simplified modelling of a hermetic scroll refrigeration compressor, Applied Thermal Engineering 22 (2002) 107–120.

E.W. Lemmon, I.H. Bell, M.L. Huber, M.O. McLinden, NIST Standard Reference Database 23: Reference Fluid Thermodynamic and Transport Properties-REFPROP, Version 10.0.

R Core Team, R: A Language and Environment for Statistical Computing, (2023).

C.C. Hiller, L.R. Glicksman, Improving heat pump performance via compressor capacity control: analysis and test, MIT Energy Lab, 1976.